HP UPS R5500 User Guide Part Number 351643-004 September 2007 (Fourth Edition)
Component identification 10 • The REPO feature immediately powers down protected devices and does not utilize the orderly shutdown procedure initia
Installation 11 Installation Precautions Save these instructions. This document contains important safety instructions that should be followed during
Installation 12 The following items are supplied with the rack: • Screws • Hex nuts • Cage nuts • Cage nut-fitting tool Selecting a site WARN
Installation 13 WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: • The leveling feet are extended to the f
Installation 14 3. Install cage nuts or clip nuts into the rear of the rack. 4. Insert screws through the mounting rail into the cage nuts or clip
Installation 15 5. Tighten the hex nuts. Preparing the rails for integrated shipping If the unit is to be shipped in an HP 9000 or 10000 series ra
Installation 16 WARNING: Uneven mechanical loading in the rack may cause a hazardous condition CAUTION: Always plan the rack installation so
Installation 17 Removing the UPS battery bracket Installing the batteries WARNING: To prevent personal injury, prepare the area and observe all
Installation 18 Replacing the UPS battery bracket Attaching the UPS front bezel
Installation 19 Switching on the UPS battery circuit breaker Connecting the serial communications port CAUTION: Use only the computer interface
© Copyright 2003, 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warra
Installation 20 Connecting the REPO port WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while connecting t
Installation 21 Separate wire pairs are attached to a single, normally-open contact in a parallel connection. HP recommends using different colors fo
Installation 22 The ground bonding cable is not included. Connecting the UPS to utility power WARNING: To prevent injury from electric shock or
Installation 23 To provide additional receptacles: • Plug a PDU or other device into the high current, large output receptacle. The large output rec
Installation 24 IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to devices. The batteries charge to: • 80 perc
Installation 25 Attaching the ERM front bezel Switching off the ERM circuit breaker WARNING: To prevent personal injury from electric shock or
Installation 26 Connecting the ERM to the UPS NOTE: To install a second ERM, plug the cable from the second ERM into the socket at the rear of
UPS operations 27 UPS operations Modes of operation The UPS has four modes of operation: • Standby mode (on page 27) • Operate mode (on page 27) •
UPS operations 28 NOTE: • If the UPS is using battery power (no utility power is present and the Utility LED is red), press and hold the On but
UPS operations 29 Available settings Parameter Associated LED Explanation (when LED is illuminated) 230 Nom Battery Fault (red) Nominal utility
Contents 3 Contents Component identification...
UPS operations 30 Silencing an audible alarm To silence an alarm, press the Test/Alarm Reset button ("UPS front panel controls" on page 7)
Power management 31 Power management Power management software HP Power Manager software ensures maximum power reliability of computer systems throu
Maintenance 32 Maintenance Removing the UPS front bezel Removing the ERM front bezel
Maintenance 33 Replacing the UPS electronics module This component is hot-swappable and can be replaced without powering down the UPS. 1. (optional
Maintenance 34 7. Replace the screw. 8. Replace the option card. 9. Reconnect the external cable to the card. 10. Verify that the UPS is configu
Maintenance 35 To replace the component, reverse the removal procedure. NOTE: Replacing the option card might require power management software
Maintenance 36 CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a backup. Do not maintain an inventory o
Maintenance 37 Replacing the UPS To remove the UPS: 1. Power down all attached load devices. 2. Power down the UPS ("Powering down the UPS&quo
Maintenance 38 3. Unplug the ERM from a second connected ERM. 4. Remove the front bezel ("Removing the ERM front bezel" on page 32) on th
Troubleshooting 39 Troubleshooting LED and audible alarm troubleshooting General Alarm LED On Battery LED Battery Fault LED Site Wiring Fau
Contents 4 Verifying the REPO port connection ...
Troubleshooting 40 Red Off Off Off Off Off On—Continuous Yes Battery condition (on page 40) Flashing red Off Off Off Flashing green Off On—Continu
Troubleshooting 41 b. Remove one or more load devices to reduce the power requirements. c. Wait at least 5 seconds and restart the UPS. d. If the
Troubleshooting 42 Overload condition All the load LEDs are illuminated. Action: 1. Power down the UPS ("Powering down the UPS" on page 30
Troubleshooting 43 UPS frequently switches between utility and battery power Action: 1. Check the input voltage and reconfigure the UPS ("Confi
Specifications 44 Specifications UPS physical specifications Parameter Value Height 13.03 cm (5.13 in) Depth 66.04 cm (26 in) Width 44.15 cm (1
Specifications 45 UPS model Load segment Circuit breaker Output receptacles Maximum current 2 x IEC-320-C13 10 A per receptacle 1 x L6-30R U
Specifications 46 Output tolerance specifications Source of power Regulation Utility power (nominal range) -10% to +6% of nominal output voltage
Specifications 47 Load, W (percent) Estimated battery runtime (minutes) Runtime with one ERM (minutes) Runtime with two ERMs (minutes) 50 15 49 85 8
Spares 48 Spares Ordering spares To order a spare, visit the HP website (http://h61003.www6.hp.com). To replace parts under warranty, contact an HP a
Spares 49 Item Description Spare part number 8 Computer interface cable 397642-001 9 Extension bars and mounting hardware 419595-001* 10 UPS un
Contents 5 UPS spare parts list...
Technical support 50 Technical support Before you contact HP Be sure to have the following information available before you call HP: • Technical su
Warranty information 51 Warranty information Limited warranty To back up the wide range of features offered with the UPS, a 3-year limited warranty
Regulatory compliance notices 52 Regulatory compliance notices Regulatory compliance identification numbers For the purpose of regulatory compliance
Regulatory compliance notices 53 energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
Regulatory compliance notices 54 Canadian notice (Avis Canadien) Class A equipment This Class A digital apparatus meets all requirements of the Cana
Regulatory compliance notices 55 Japanese notice BSMI notice Battery replacement notice WARNING: Power products contain sealed lead-acid bat
Regulatory compliance notices 56 Taiwan battery recycling notice The Taiwan EPA requires dry battery manufacturing or importing firms in accordance
Electrostatic discharge 57 Electrostatic discharge Preventing electrostatic discharge To prevent damaging the system, be aware of the precautions yo
Acronyms and abbreviations 58 Acronyms and abbreviations ERM extended runtime module LED light-emitting diode NEC National Electrical Code NEMA N
Index 59 A alarm cannot be silenced 39 alarm conditions 39 alarms, silencing 30 alarms, troubleshooting 39 authorized reseller 50 Auto-Bypa
Component identification 6 Component identification UPS R5500 overview The HP UPS R5500 features a 3U rack-mount design and offers power protection
Index 60 G general alarm condition 40 General Alarm LED, location 8 General Alarm LED, troubleshooting 39 ground bonding cable, connecting 21
Index 61 REPO port, connecting 20 REPO port, location 9 REPO port, overview 9 REPO port, specifications 47 REPO port, verifying connection
Component identification 7 UPS front panel controls The front panel is shown with the bezel removed. Item Description Function 1 On button
Component identification 8 UPS front panel LED indicators The front panel is shown with the bezel removed. Item LED description 1 Overload
Component identification 9 UPS rear panel Item Description 1 REPO port 2 Ground bonding screw 3 Communications port/option slot 4 Load segmen