
Web interface 10
Alarms menu
Click Alarms in the left navigation frame to display the Alarms screen. The active alarms are listed by the date
and time at which the alarm most recently occurred. The active alarm is removed from the Alarms screen
when cleared but is recorded in the Alarm Log.
The following information appears for each alarm:
• Severity—An icon indicating the severity or status of the alarm (Critical, Warning, Normal, Unknown,
or Information)
• Description of Alarm—The name of the alarm (For more information on the alarm description, see
"Warning and alarm messages (on page 10).")
• Date/Time—The date and time at which the alarm occurred
On the Alarms screen, click Refresh to update the screen with current information.
Warning and alarm messages
The following tables describe the possible warning and alarm messages that the MCS 5042 unit sends to the
management module. These messages appear on the operator display and on the web interface Alarms
menu and Alarm History menu (on page 20).
Fan unit failed or not installed
Indicators Meaning
Operator display alarm message
Fan 1, 2, 3, 4, 5, or 6 Failed
Web interface alarm message
Fan 1, 2, 3, 4, 5, or 6 Failed or Not Installed
Condition
Fan 1, 2, 3, 4, 5, or 6 is running at less than the minimum RPM
Sensors
Fan 1, 2, 3, 4, 5, or 6
SNMP notification
Warning
Type of message
Warning
Solution:
1. Remove the fan unit.
Comentarios a estos manuales