User Service Guide HP Integrity Superdome/sx2000 ServerSecond EditionManufacturing Part Number : A9834-9001BSeptember 2006

Pagina 3 - Contents

Chapter 3Installing the SystemSetting Up the System100Figure 3-23 Installing the Rear Blower BezelStep 3. Align the bezel over the nuts that are attac

Pagina 4

Chapter 3Installing the SystemSetting Up the System101Figure 3-24 Installing the Front Blower BezelStep 3. Align the bezel over the nuts that are atta

Pagina 5

Chapter 3Installing the SystemSetting Up the System102• Required method of grounding is to connect the green power cord safety ground to the site grou

Pagina 6

Chapter 3Installing the SystemSetting Up the System103Installing and Verifying the PDCAAll systems are delivered with the appropriate cable plug for o

Pagina 7

Chapter 3Installing the SystemSetting Up the System104Figure 3-25 PDCA Assembly for Options 6 and 7Figure 3-26 A 4-Wire ConnectorL2 L1L3 PE

Pagina 8

Chapter 3Installing the SystemSetting Up the System105Figure 3-27 A 5-Wire ConnectorUse the following procedure to install the PDCA:WARNING Make sure

Pagina 9

Chapter 3Installing the SystemSetting Up the System106Figure 3-28 Installing the PDCAStep 4. Using a T-20 driver, attach the four screws that hold the

Pagina 10

Chapter 3Installing the SystemSetting Up the System107Figure 3-29 Checking PDCA Test Points (5-Wire)Table 3-3 4- and 5-Wire Voltage Ranges4-Wire 5-Wir

Pagina 11

Chapter 3Installing the SystemSetting Up the System108Voltage Check The voltage check ensures that all phases (and neutral, for international systems)

Pagina 12

Chapter 3Installing the SystemSetting Up the System109WARNING SHOCK HAZARDRisk of shock hazard while testing primary power.Use properly insulated prob

Pagina 13

Figures11Figure 1-1. Superdome Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Fi

Pagina 14

Chapter 3Installing the SystemSetting Up the System110Removing the EMI PanelsRemove the front and back electromagnetic interference (EMI) panels to ac

Pagina 15 - About This Document

Chapter 3Installing the SystemSetting Up the System111Figure 3-33 Removing the Back EMI PanelStep 4. Use the handle provided to gently remove the EMI

Pagina 16 - Intended Audience

Chapter 3Installing the SystemSetting Up the System112Figure 3-34 Cable LabelingRouting the I/O CablesRouting the cables is a significant task in the

Pagina 17 - Typographic Conventions

Chapter 3Installing the SystemSetting Up the System113Figure 3-35 Routing I/O CablesUse the following procedure and guidelines to route cables through

Pagina 18 - Related Information

Chapter 3Installing the SystemSetting Up the System114Step 3. Connect the management processor cables last.Step 4. Reattach the cable access plate at

Pagina 19 - Publishing History

Chapter 3Installing the SystemInstalling the Support Management Station115Installing the Support Management StationThe Support Management Station (SMS

Pagina 20 - HP Encourages Your Comments

Chapter 3Installing the SystemConfiguring the Event Information Tools116Configuring the Event Information ToolsThere are three tools included in the E

Pagina 21 - 1 Overview

Chapter 3Installing the SystemTurning On Housekeeping Power117Turning On Housekeeping PowerUse the following procedure to turn on housekeeping power t

Pagina 22

Chapter 3Installing the SystemTurning On Housekeeping Power118Figure 3-36 Front Panel with Housekeeping (HKP) Power On and Present LEDsStep 5. Examine

Pagina 23

Chapter 3Installing the SystemTurning On Housekeeping Power119Figure 3-37 BPS LEDsBPS LEDs

Pagina 24 - Server Components

Figures12Figure 3-31. Power Supply Indicator LED Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109Figure 3-32.

Pagina 25 - Figure 1-1 Superdome Cabinet

Chapter 3Installing the SystemConnecting the MP to the Customer LAN120Connecting the MP to the Customer LANThis section discusses how to connect, set

Pagina 26 - Power System

Chapter 3Installing the SystemConnecting the MP to the Customer LAN121Setting the Customer IP AddressNOTE The default IP address for the customer LAN

Pagina 27 - Enabling 48 Volts

Chapter 3Installing the SystemConnecting the MP to the Customer LAN122This is the host name for the customer LAN. You can use any name you like. The n

Pagina 28 - Cooling System

Chapter 3Installing the SystemBooting and Verifying the System123Booting and Verifying the SystemAfter installing the system, verify that the proper h

Pagina 29

Chapter 3Installing the SystemBooting and Verifying the System124The MP Main Menu appears as shown in Figure 3-42.Figure 3-42 Main MP MenuStep 3. Repe

Pagina 30 - Utilities Subsystem

Chapter 3Installing the SystemBooting and Verifying the System125Figure 3-44 MP Virtual Front PanelStep 6. From the VFP menu, enter s to select the wh

Pagina 31 - CLU Functionality

Chapter 3Installing the SystemBooting and Verifying the System126Figure 3-46 MP Console OptionPowering On the System 48 V SupplyStep 1. Switch on the

Pagina 32 - System Clocks

Chapter 3Installing the SystemBooting and Verifying the System127Booting the HP Integrity Superdome/sx2000 to a EFI ShellAfter powering on or using th

Pagina 33 - Compact Flash

Chapter 3Installing the SystemBooting and Verifying the System128Figure 3-48 EFI Shell PromptNOTE If autoboot is enabled for an nPartition, you must i

Pagina 34 - Figure 1-4 HUCB

Chapter 3Installing the SystemBooting and Verifying the System129Figure 3-49 HP Integrity Superdome/sx2000 Partitions at System Firmware ConsoleVerify

Pagina 35 - Backplane (Fabric)

Figures13Figure C-16. Power Status First Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226Figure C-1

Pagina 36 - Clock Subsystem

Chapter 3Installing the SystemBooting and Verifying the System130Step 2. At the Select Device: prompt, enter b then the cabinet number to check the po

Pagina 37

Chapter 3Installing the SystemBooting and Verifying the System131IMPORTANT An asterisk (*) appears in the MP column only for cabinet 0; that is, the c

Pagina 38

Chapter 3Installing the SystemRunning JET Software132Running JET SoftwareEnsure that the network diagnostic is enabled at the MP prompt; MP:CM>nd.

Pagina 39 - Cabinet ID

Chapter 3Installing the SystemOffline Diagnostic Environment (ODE)133Offline Diagnostic Environment (ODE)Now that scan has been run, you can run all t

Pagina 40

Chapter 3Installing the SystemAttaching the Rear Kick Plates134Attaching the Rear Kick PlatesKick plates protect cables from accidentally being discon

Pagina 41 - CPUs and Memories

Chapter 3Installing the SystemPerforming a Visual Inspection and Completing the Installation135Performing a Visual Inspection and Completing the Insta

Pagina 42 - Cell Memory System

Chapter 3Installing the SystemPerforming a Visual Inspection and Completing the Installation136Step 4. Reinstall the front EMI panel (Figure 3-55).Fig

Pagina 43 - Figure 1-9 Cell Memory

Chapter 3Installing the SystemPerforming a Visual Inspection and Completing the Installation137a. Align the lip inside the cabinet with the lip on the

Pagina 44

Chapter 3Installing the SystemConducting a Post Installation Check138Conducting a Post Installation CheckAfter the system has been installed in a comp

Pagina 45

Chapter 41394 Booting and Shutting Down the Operating SystemThis chapter presents procedures for booting an operating system (OS) on an nPartition (ha

Pagina 47 - Cell OL*

Chapter 4Booting and Shutting Down the Operating SystemOperating Systems Supported on Cell-based HP Servers140Operating Systems Supported on Cell-base

Pagina 48 - I/O Subsystem

Chapter 4Booting and Shutting Down the Operating SystemSystem Boot Configuration Options141System Boot Configuration OptionsThis section briefly discu

Pagina 49 - Figure 1-10 I/O Rope Mapping

Chapter 4Booting and Shutting Down the Operating SystemSystem Boot Configuration Options142Manager utility) to manage boot options for your system dis

Pagina 50

Chapter 4Booting and Shutting Down the Operating SystemSystem Boot Configuration Options143To set the ACPI configuration value, issue the acpiconfig v

Pagina 51

Chapter 4Booting and Shutting Down the Operating SystemSystem Boot Configuration Options144CAUTION An nPartition on an HP Integrity server cannot boot

Pagina 52 - New Server Cabling

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX145Booting and Shutting Down HP-UXThis section presents procedur

Pagina 53 - Figure 1-11 Backplane Cables

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX146To add an HP-UX boot option when logged in to HP-UX, use the

Pagina 54 - Firmware

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX147CAUTION ACPI Configuration for HP-UX Must Be defaultOn cell-b

Pagina 55 - Server Configurations

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX148HP-UX Booting (EFI Shell)From the EFI Shell environment, to b

Pagina 56 - Server Errors

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX149To boot the HP-UX OS, do not type anything during the 10-seco

Pagina 57 - Error Logging

15About This DocumentThis document contains a system overview, system specific parameters, how to install the system, and operating system specifics

Pagina 58

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX150Step 4. Boot to the HP-UX Boot Loader prompt (HPUX>) by pr

Pagina 59 - 2 System Specifications

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX151Step 1. Access the EFI Shell environment for the nPartition o

Pagina 60 - Dimensions and Weights

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP-UX152Log in to the management processor for the server and use the

Pagina 61 - Component Weights

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP OpenVMS I64153Booting and Shutting Down HP OpenVMS I64This section

Pagina 62

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP OpenVMS I64154To configure booting on Fibre Channel devices, you m

Pagina 63 - Electrical Specifications

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP OpenVMS I64155To exit the EFI environment, press ^B (Control+B); t

Pagina 64

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP OpenVMS I64156Booting HP OpenVMS (EFI Shell)From the EFI Shell env

Pagina 65 - System Power Requirements

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down HP OpenVMS I64157Log in to the management processor (MP) for the serv

Pagina 66 - Component Power Requirements

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Microsoft Windows158Booting and Shutting Down Microsoft WindowsThis s

Pagina 67 - Management Station)

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Microsoft Windows159Adding a Microsoft Windows Boot OptionThis proced

Pagina 68 - Environmental Requirements

16Intended AudienceThis document is intended for HP trained Customer Support Consultants.Document OrganizationThis document is organized as follows:Ch

Pagina 69 - Configurations

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Microsoft Windows160Step 6. Press Q to quit the NVRBOOT utility, and

Pagina 70

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Microsoft Windows161Step 3. Press Enter to initiate booting using the

Pagina 71

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Microsoft Windows162/a Abort a system shutdown./t xxxSet the timeout

Pagina 72 - Acoustic Noise Specification

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux163Booting and Shutting Down LinuxThis section presents procedur

Pagina 73 - Airflow exit (300 CFM)

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux164See “Boot Options List” on page 141 for additional informatio

Pagina 74

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux165Booting Red Hat Enterprise LinuxYou can boot the Red Hat Ente

Pagina 75 - 3 Installing the System

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux166From the system console, select the EFI Shell entry from the

Pagina 76 - Introduction

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux167Refer to the procedure “Booting SuSE Linux Enterprise Server

Pagina 77 - Checking the Inventory

Chapter 4Booting and Shutting Down the Operating SystemBooting and Shutting Down Linux168Use the PE command at the management processor Command Menu t

Pagina 78

Appendix A169A sx2000 LEDs

Pagina 79

17Typographic ConventionsThe following typographic conventions are used in this publication.WARNING A warning lists requirements that you must meet t

Pagina 80

Appendix Asx2000 LEDs170Table A-1 Front Panel LEDsLED Driven By State Meaning48V Good PM On (green) 48V is goodHKP Good PM On (green) Housekeeping is

Pagina 81

Appendix Asx2000 LEDs171Table A-2 Power and OL* LEDsLED LocationDriven ByState MeaningCell Power Chassis beside cell, and on cellCell LPM On Green HKP

Pagina 82

Appendix Asx2000 LEDs172Figure A-1 Utilities LEDsHot swap oscillators (HSO)System Backplane RPM On GreenOn YellowHSO Supply runningHSO clock faultTabl

Pagina 83 - Installing the System

Appendix Asx2000 LEDs173Figure A-2 PDH StatusA label will be placed on the outside of the SDCPB Frame to indicated PDH Status, DC/DC Converter faults

Pagina 84

Appendix Asx2000 LEDs174

Pagina 85

Appendix B175B Management Processor CommandsThis Appendix summarizes the Management Processor commands. Notice that in the examples herein, MP is used

Pagina 86

Appendix BManagement Processor CommandsMP Command: BO176MP Command: BOBO - Boot partition• Access level—Single PD user• Scope—partitionThis command bo

Pagina 87

Appendix BManagement Processor CommandsMP Command: CA177MP Command: CACA - Configure Asynchronous & Modem Parameters• Access level—Operator• Scope

Pagina 88 - Unpacking the PDCA

Appendix BManagement Processor CommandsMP Command: CC178MP Command: CCCC - Complex Configuration• Access level—Administrator• Scope—ComplexThis comman

Pagina 89 - Returning Equipment

Appendix BManagement Processor CommandsMP Command: CP179MP Command: CPCP - Cells Assigned by Partition• Access Level - Single Partition User•Scope - C

Pagina 90

18Related InformationYou can find other information on HP server hardware management, Microsoft® Windows®, and diagnostic support tools at the followi

Pagina 91 - Setting Up the System

Appendix BManagement Processor CommandsMP Command: DATE180MP Command: DATEDATE Command - Set Date and Time.• Access level—Administrator• Scope—Complex

Pagina 92

Appendix BManagement Processor CommandsMP Command: DC181MP Command: DCDC - Default Configuration• Access level—Administratrix• Scope—ComplexThis comma

Pagina 93

Appendix BManagement Processor CommandsMP Command: DF182MP Command: DFDF - Display FRUID• Access level—Single Partition User• Scope—ComplexThis comman

Pagina 94

Appendix BManagement Processor CommandsMP Command: DI183MP Command: DIDI - Disconnect Remote or LAN Console• Access level—Operator• Scope—ComplexThis

Pagina 95

Appendix BManagement Processor CommandsMP Command: DL184MP Command: DLDL - Disable LAN Access• Access level—Administrator• Scope—ComplexThis command d

Pagina 96

Appendix BManagement Processor CommandsMP Command: EL185MP Command: ELDL - Enable LAN Access• Access level—Administrator• Scope—ComplexThis command en

Pagina 97

Appendix BManagement Processor CommandsMP Command: HE186MP Command: HEHE - Help Menu•Scope—N/A• Access level—Single PD userThis command displays a lis

Pagina 98

Appendix BManagement Processor CommandsMP Command: HE187Example B-11 HE Command

Pagina 99

Appendix BManagement Processor CommandsMP Command: ID188MP Command: IDID - Configure Complex Identification• Access level—Operator• Scope—ComplexThis

Pagina 100

Appendix BManagement Processor CommandsMP Command: IO189MP Command: IOIO - Display Connectivity Between Cells and I/O• Access level—Sinfle Partition U

Pagina 101 - Wiring Check

19Publishing HistoryThe publishing history of this document includes the following editions. Updates are made to this document on an unscheduled as n

Pagina 102

Appendix BManagement Processor CommandsMP Command: IT190MP Command: ITIT - View / Configure Inactivity Timeout Parameters• Access level—Operator• Scop

Pagina 103

Appendix BManagement Processor CommandsMP Command: LC191MP Command: LCLC - LAN Configuration• Access level—Administrator• Scope—ComplexThis command di

Pagina 104

Appendix BManagement Processor CommandsMP Command: LS192MP Command: LSLS - LAN Status• Access level—Single Partition User• Scope—ComplexThis command d

Pagina 105

Appendix BManagement Processor CommandsMP Command: MA193MP Command: MAMA - Main Menu• Access level—Single Partition User•Scope—N/AThe command takes th

Pagina 106

Appendix BManagement Processor CommandsMP Command: ND194MP Command: NDND - Network Diagnostics• Access level—Administrator• Scope—ComplexThis command

Pagina 107

Appendix BManagement Processor CommandsMP Command: PD195MP Command: PDPD - Set Default Partition• Access level—Operator• Scope—ComplexThis command set

Pagina 108 - Voltage Check

Appendix BManagement Processor CommandsMP Command: PE196MP Command: PEPE - Power Entity• Access level—Operator• Scope—ComplexThis command turns power

Pagina 109

Appendix BManagement Processor CommandsMP Command: PE197I - IO ChassisP - PartitionSelect Device: p# Name--- ----0) Partition 01) Partition 12) Partit

Pagina 110 - Removing the EMI Panels

Appendix BManagement Processor CommandsMP Command: PS198MP Command: PSPS - Power and Configuration Status• Access level—Single Partition User• Scope—C

Pagina 111 - Connecting the Cables

Appendix BManagement Processor CommandsMP Command: PS199Example B-20 PS Command

Pagina 112 - Routing the I/O Cables

2Legal Notices Copyright 2006 Hewlett-Packard Development Company, L.P.The information contained herein is subject to change without notice.The only

Pagina 113

20HP Encourages Your CommentsHP welcomes your feedback on this publication. Address your comments to [email protected] and note that you will n

Pagina 114

Appendix BManagement Processor CommandsMP Command: RE200MP Command: RERE - Reset Entity• Access level—Operator• Scope—ComplexThis command resets the s

Pagina 115

Appendix BManagement Processor CommandsMP Command: RL201MP Command: RLRL - Re-key Complex Profile Lock• Access level—Operator• Scope—ComplexThis comma

Pagina 116

Appendix BManagement Processor CommandsMP Command: RR202MP Command: RRRR - Reset Partition for Re-configuration• Access level—Single Partition User• S

Pagina 117 - Turning On Housekeeping Power

Appendix BManagement Processor CommandsMP Command: RS203MP Command: RSRS - Reset Partition• Access level—Single PD user• Scope—PartitionThis command r

Pagina 118

Appendix BManagement Processor CommandsMP Command: SA204MP Command: SASA - Set Access Parameters• Access level—Administrator• Scope—ComplexThis comman

Pagina 119 - Figure 3-37 BPS LEDs

Appendix BManagement Processor CommandsMP Command: SO205MP Command: SOSO - Security Options and Access Control Configuration• Access level—Administrat

Pagina 120

Appendix BManagement Processor CommandsMP Command: SYSREV206MP Command: SYSREVSYSREV - Display System and Manageability Firmware Revisions• Access lev

Pagina 121

Appendix BManagement Processor CommandsMP Command: TC207MP Command: TCTC - TOC Partition• Access level—Single Partition User• Scope—PartitionThis comm

Pagina 122

Appendix BManagement Processor CommandsMP Command: TE208MP Command: TETE - Tell• Access level—Single Partition User• Scope—ComplexThis command treats

Pagina 123

Appendix BManagement Processor CommandsMP Command: VM209MP Command: VMVM - Voltage Margin• Access level—Single Partition User• Scope—CabinetThe comman

Pagina 124 - Figure 3-42 Main MP Menu

Chapter 1211 OverviewThe HP superscalable sx2000 processor chipset is the new chipset for the Superdome high-end platform. It supports up to 128 PA-RI

Pagina 125

Appendix BManagement Processor CommandsMP Command: WHO210MP Command: WHOWHO - Display List of Connected Users• Access level—Single Partition User• Sco

Pagina 126 - Figure 3-46 MP Console Option

Appendix BManagement Processor CommandsMP Command: XD211MP Command: XDXD - Diagnostic and Reset of MP• Access level—Operator• Scope—ComplexThis comman

Pagina 127 - Enter. Do

Appendix BManagement Processor CommandsMP Command: XD212

Pagina 128 - Figure 3-48 EFI Shell Prompt

Appendix C213C Powering the System On and Off This appendix provides procedures to shut down and bring up a system. Chose the appropriate section for

Pagina 129 - Verifying the System

Appendix CPowering the System On and OffShutting Down the System214Shutting Down the SystemUse this procedure whenever the system must be shut down.Ch

Pagina 130

Appendix CPowering the System On and OffShutting Down the System215Figure C-2 Main MP MenuStep 3. Invoke the Command Menu by entering cm at the MP pro

Pagina 131

Appendix CPowering the System On and OffShutting Down the System216Step 5. Read the and save the current system configuration by entering cp and the C

Pagina 132 - Running JET Software

Appendix CPowering the System On and OffShutting Down the System217Step 8. From the VFP, enter s to select the whole system or enter the partition num

Pagina 133

Appendix CPowering the System On and OffShutting Down the System218• Windows: Log in as Administrator. From the Special Administration Console (SAC>

Pagina 134

Appendix CPowering the System On and OffShutting Down the System219Step 6. Read the Cell PDH Controller status to determine if the partition is at BIB

Pagina 135

Chapter 1Overview22- A new cell board- A new system backplane and it’s power board- A new I/O backplanes and it’s power board- New I/O - backplane cab

Pagina 136

Appendix CPowering the System On and OffShutting Down the System220Step 1. From the Command Menu, enter pe (Figure C-10).Figure C-10 Power Entity Comm

Pagina 137

Appendix CPowering the System On and OffShutting Down the System221Step 5. Enter b at the select device prompt to select ensure that the cabinet power

Pagina 138

Appendix CPowering the System On and OffTurning On Housekeeping Power222Turning On Housekeeping PowerUse the following procedure to turn on housekeepi

Pagina 139 - Chapter 4

Appendix CPowering the System On and OffTurning On Housekeeping Power223Figure C-13 Front Panel Display with Housekeeping (HKP) Power On, and Present

Pagina 140

Appendix CPowering the System On and OffTurning On Housekeeping Power224Figure C-14 BPS LEDsBPS LEDs

Pagina 141

Appendix CPowering the System On and OffPowering On the System Using the pe Command225Powering On the System Using the pe CommandThis section describe

Pagina 142

Appendix CPowering the System On and OffPowering On the System Using the pe Command226Step 4. From the CM> prompt, enter ps to observe the power st

Pagina 143

Appendix D227D TemplatesThis appendix contains blank floor plan grids and equipment templates. Combine the necessary number of floor plan grid sheets

Pagina 144

Appendix DTempl atesTemplates228TemplatesThis section contains blank floor plan grids and equipment templates. Combine the necessary number of floor p

Pagina 145

Appendix DTemplatesTemplates229Figure D-3 on page 231 illustrates the overall dimensions required for an SD64 complex.Figure D-1 Cable Cutouts and Cas

Pagina 146 - Booting HP-UX

Chapter 1OverviewServer History and Specifications23Server History and SpecificationsSuperdome was introduced as the new platform architecture for HP

Pagina 147

Appendix DTempl atesTemplates230Figure D-2 SD16 and SD32 Space Requirements

Pagina 148 - , fs1:, and so on

Appendix DTemplatesTemplates231Figure D-3 SD64 Space RequirementsEquipment Footprint TemplatesEquipment footprint templates are drawn to the same scal

Pagina 149

Appendix DTempl atesTemplates232NOTE Photocopying typically changes the scale of copied drawings. If any templates are copied, then all templates and

Pagina 150

Appendix DTemplatesTemplates233Figure D-4 Computer Floor Template

Pagina 151 - Shutting Down HP-UX

Appendix DTempl atesTemplates234Figure D-5 Computer Floor Template

Pagina 152

Appendix DTemplatesTemplates235Figure D-6 Computer Floor Template

Pagina 153

Appendix DTempl atesTemplates236Figure D-7 Computer Floor Template

Pagina 154

Appendix DTemplatesTemplates237Figure D-8 Computer Floor Template

Pagina 155 - Booting HP OpenVMS

Appendix DTempl atesTemplates238Figure D-9 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 156

Appendix DTemplatesTemplates239Figure D-10 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 157

Chapter 1OverviewServer Components24Server ComponentsA Superdome system consists of the following types of cabinet assemblies:At least one Superdome l

Pagina 158

Appendix DTempl atesTemplates240Figure D-11 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 159

Appendix DTemplatesTemplates241Figure D-12 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 160 - Booting Microsoft Windows

Appendix DTempl atesTemplates242Figure D-13 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 161

Appendix DTemplatesTemplates243Figure D-14 SD32 and SD64, and I/O Expansion Cabinet Templates

Pagina 162

Appendix DTempl atesTemplates244

Pagina 163

245IndexAac powervoltage check, 108wiring check, 101ac power verification4-wire PDCA, 1035-wire PDCA, 103AC0 Present LED, 118, 223AC1 Present LED, 118

Pagina 164

Index246interferencecommunications, 76inventory check, 77IP addressdefault values, 121LAN configuration screen, 121setting private and customer LAN, 1

Pagina 165

Index247Wwiring check, 101wrist strap usage, 76

Pagina 166

Chapter 1OverviewServer Components25When the PA dual-core or the IA dual-core processors are used, the CPU counts are doubled by the use of the dual-d

Pagina 167 - Shutting Down Linux

Chapter 1OverviewPower System26Power SystemThe power subsystem consists of the following components:- 1 or 2 Power Distribution Component Assembly (PD

Pagina 168

Chapter 1OverviewPower System27- Inline connector: Mennekes ME532C6-16, 3-phase, 5-wire, 32 Amps, 450/475 V, VDE certified, color red,IEC309-1, IEC309

Pagina 169 - A sx2000 LEDs

Chapter 1OverviewCooling System28Cooling SystemThe Superdome has four blowers and five I/O fans per cabinet. These components are all hot-swap devices

Pagina 170 - Table A-1 Front Panel LEDs

Chapter 1OverviewCooling System29If the failure causes a transition to N- I/O or main fans in a CPU cabinet, the cabinet is immediately powered off. I

Pagina 171 - Table A-2 Power and OL* LEDs

Contents31. OverviewServer History and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 172 - Table A-3 OL* LED States

Chapter 1OverviewUtilities Subsystem30Utilities SubsystemThe Superdome utilities subsystem is comprised of a number of hardware and firmware component

Pagina 173 - Figure A-2 PDH Status

Chapter 1OverviewUtilities Subsystem31- Supports USB for keyboard and mouse at boot- Supports VGA during boot- Enables global shared memory (GSM)- Sup

Pagina 174 - Appendix A

Chapter 1OverviewUtilities Subsystem32- Status LEDs for the SBA cable OL*, the cell OL*, and the I/O backplane OL*PM3 FunctionalityThe PM3 performs th

Pagina 175 - Management Processor Commands

Chapter 1OverviewUtilities Subsystem33-The ability to process and store log entries (chassis codes)- Console functions to every partition- OL* functio

Pagina 176 - MP Command: BO

Chapter 1OverviewUtilities Subsystem34HUCBThe HUCB, shown in Figure 1-4, is the backplane of the utility subsystem. It provides cable distribution for

Pagina 177 - MP Command: CA

Chapter 1OverviewBackplane (Fabric)35Backplane (Fabric)The system backplane assembly provides the following functionality in an sx2000 system:- Interf

Pagina 178 - MP Command: CC

Chapter 1OverviewBackplane (Fabric)36an additional crossbar in a second backplane for a dual backplane configuration. The connection is through a high

Pagina 179 - MP Command: CP

Chapter 1OverviewBackplane (Fabric)37System Clock DistributionThe following system components receive the system clock are the eight cell boards that

Pagina 180 - MP Command: DATE

Chapter 1OverviewBackplane (Fabric)38The HSO connects to the system backplane through an HMZD2X10 right-angle receptacle.sx2000 RCS ModuleThe sx2000 R

Pagina 181 - MP Command: DC

Chapter 1OverviewBackplane (Fabric)39If one of the HSOs outputs does not have the correct amplitude then the RCS uses the other one as the source of c

Pagina 182 - MP Command: DF

Contents4Hardware Corrected Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 183 - MP Command: DI

Chapter 1OverviewBackplane (Fabric)40The backplane has two slots for power supply modules. The power supply connector for each slot has a 1-bit slot a

Pagina 184 - MP Command: DL

Chapter 1OverviewCPUs and Memories41CPUs and MemoriesThe cell provides the processing and memory resources required by each sx2000 system configuratio

Pagina 185 - MP Command: EL

Chapter 1OverviewCPUs and Memories42The remote I/O link provides a self-correcting, high-speed communication pathway between the cell and the I/O subs

Pagina 186 - MP Command: HE

Chapter 1OverviewCPUs and Memories43platforms may support DIMMs based on non monolithic (or stacked) DRAMs, which are incompatible with the sx2000. Th

Pagina 187 - Example B-11 HE Command

Chapter 1OverviewCPUs and Memories44industry-standard DIMM. This increase in height allows the DIMM to accommodate twice as many DRAMs as an industry-

Pagina 188 - MP Command: ID

Chapter 1OverviewCPUs and Memories45- Cellmap (across cells)- Link (across fabrics)Memory Bank Attribute Table The MBAT interleaving is done on a per

Pagina 189 - MP Command: IO

Chapter 1OverviewCPUs and Memories46Memory Error ProtectionAll of the CC cache lines are protected in memory by an error correction code (ECC). The sx

Pagina 190 - MP Command: IT

Chapter 1OverviewCPUs and Memories47Platform Dependant HardwareThe platform dependent hardware's (PDH) includes functionality that is required by

Pagina 191 - MP Command: LC

Chapter 1OverviewI/O Subsystem48I/O SubsystemThe sx2000 I/O backplane (SIOBP) is an update of the sx1000 I/O backplane, with a new set of chips that i

Pagina 192 - MP Command: LS

Chapter 1OverviewI/O Subsystem49SBA Chip: CC-to-RopesThe SBA chip communicates with the CC on the cell board via a pair of high-speed serial unidirect

Pagina 193 - MP Command: MA

Contents5Installing and Verifying the PDCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103V

Pagina 194 - MP Command: ND

Chapter 1OverviewI/O Subsystem50PCI SlotsFor maximum performance and availability, each PCI slot is sourced by its own LBA chip and is supported by it

Pagina 195 - MP Command: PD

Chapter 1OverviewI/O Subsystem51together 5.V +3.3 V auxilary will be on whenever AC is applied. The SIOBP FPGA is responsible for ensuring that each v

Pagina 196 - MP Command: PE

Chapter 1OverviewNew Server Cabling52New Server CablingMost of the Superdome cables remain unchanged except three cables designed for the sx2000 to im

Pagina 197

Chapter 1OverviewNew Server Cabling53Figure 1-11 Backplane Cables

Pagina 198 - MP Command: PS

Chapter 1OverviewFirmware54FirmwareThe newer Intel Itanium® Processor firmware consists of many components loosely coupled by a single framework. The

Pagina 199 - Example B-20 PS Command

Chapter 1OverviewServer Configurations55Server ConfigurationsRefer to the HP System Partitions Guide (5990-8170A) for extensive details on the topic o

Pagina 200 - MP Command: RE

Chapter 1OverviewServer Errors56Server ErrorsTo support high availability (HA), the new chipset has included functionality to do error correction, det

Pagina 201 - MP Command: RL

Chapter 1OverviewServer Errors57are opened between PDs when it is established that the PDs are up and communication between them is open. When there i

Pagina 202 - MP Command: RR

Chapter 1OverviewServer Errors581. Detection is the hardware checks that realize an error has occurred. 2. Transaction handling modifies how the hardw

Pagina 203 - MP Command: RS

Chapter 2592 System SpecificationsThe following specifications are based on ASHRAE Class 1. Class 1 is a controlled computer room environment, in whic

Pagina 204 - MP Command: SA

Contents6Booting Red Hat Enterprise Linux . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165Bo

Pagina 205 - MP Command: SO

Chapter 2System SpecificationsDimensions and Weights60Dimensions and WeightsThis section contains server component dimensions and weights for the syst

Pagina 206 - MP Command: SYSREV

Chapter 2System SpecificationsDimensions and Weights61Component WeightsTable 2-3 lists the server and component weights. Table 2-4 lists the weights f

Pagina 207 - MP Command: TC

Chapter 2System SpecificationsDimensions and Weights62Shipping Dimensions and WeightsTable 2-5 lists the dimensions and weights of the Support Managem

Pagina 208 - MP Command: TE

Chapter 2System SpecificationsElectrical Specifications63Electrical SpecificationsThe following specifications are based on ASHRAE Class 1. Class 1 is

Pagina 209 - MP Command: VM

Chapter 2System SpecificationsElectrical Specifications64NOTE A qualified electrician must wire the PDCA receptacle to site power using copper wire an

Pagina 210 - MP Command: WHO

Chapter 2System SpecificationsElectrical Specifications65Figure 2-1 PDCA LocationsSystem Power RequirementsTable 2-8 and Table 2-9 list the ac power r

Pagina 211 - MP Command: XD

Chapter 2System SpecificationsElectrical Specifications66WARNING Beware of shock hazard. When connecting or removing input power wiring, always connec

Pagina 212

Chapter 2System SpecificationsElectrical Specifications67I/O Expansion Cabinet Power CordsTable 2-12 lists the power cords for the I/O expansion cabin

Pagina 213

Chapter 2System SpecificationsEnvironmental Requirements68Environmental RequirementsThis section provides the environmental, power dissipation, noise

Pagina 214 - Shutting Down the System

Chapter 2System SpecificationsEnvironmental Requirements69WARNING Do not connect a 380 to 415 V ac supply to a 4-wire PDCA. This is a safety hazard an

Pagina 215 - Figure C-2 Main MP Menu

Contents7Powering Off the System Using the pe Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219Turning On Hou

Pagina 216

Chapter 2System SpecificationsEnvironmental Requirements70b. These numbers are valid only for the specific configurations shown. Any upgrades may requ

Pagina 217

Chapter 2System SpecificationsEnvironmental Requirements71b. These numbers are valid only for the specific configurations shown. Any upgrades may requ

Pagina 218

Chapter 2System SpecificationsEnvironmental Requirements72Acoustic Noise SpecificationThe acoustic noise specifications are as follows:• 8.2 bel (soun

Pagina 219

Chapter 2System SpecificationsEnvironmental Requirements73AirflowHP Integrity Superdome/sx2000 systems require the cabinet air intake temperature to b

Pagina 220

Chapter 2System SpecificationsEnvironmental Requirements74Table 2-17 Physical Environmental SpecificationsConditionVoltage 200–240 VacAirflow, Nomina

Pagina 221

Chapter 3753 Installing the SystemThis chapter describes installation of an HP Integrity Superdome/sx2000 system. Installers must have received adequa

Pagina 222

Chapter 3Installing the SystemIntroduction76Introduction The instructions in this chapter are written for Customer Support Consultants (CSC) who are e

Pagina 223 - Present LEDs

Chapter 3Installing the SystemUnpacking and Inspecting the System77Unpacking and Inspecting the SystemThis section describes what to do before unpacki

Pagina 224 - Figure C-14 BPS LEDs

Chapter 3Installing the SystemUnpacking and Inspecting the System78Inspecting the Shipping Containers for DamageHP shipping containers are designed to

Pagina 225

Chapter 3Installing the SystemUnpacking and Inspecting the System79Figure 3-1 Normal Tilt IndicatorFigure 3-2 Abnormal Tilt Indicator NOTE If the til

Pagina 226

Contents8

Pagina 227 - D Templates

Chapter 3Installing the SystemUnpacking and Inspecting the System80Inspection Precautions• When the shipment arrives, check each container against the

Pagina 228 - Templates

Chapter 3Installing the SystemUnpacking and Inspecting the System81Unpacking the CabinetWARNING Use three people to unpack the cabinet safely.HP recom

Pagina 229 - Appendix D

Chapter 3Installing the SystemUnpacking and Inspecting the System82Figure 3-4 Cutting Polystrap BandsStep 3. Lift the cardboard corrugated top cap off

Pagina 230 - Templ ates

Chapter 3Installing the SystemUnpacking and Inspecting the System83Figure 3-5 Removing the Ramps from the PalletRamps

Pagina 231 - Equipment Footprint Templates

Chapter 3Installing the SystemUnpacking and Inspecting the System84Step 7. Remove the plastic anti-static bag by lifting it straight up off the cabine

Pagina 232 - Computer Room Layout Plan

Chapter 3Installing the SystemUnpacking and Inspecting the System85Step 3. Verify that the I/O chassis mounting screws are in place and secure (Figure

Pagina 233

Chapter 3Installing the SystemUnpacking and Inspecting the System86Figure 3-8 Shipping Strap LocationStep 2. Remove the pallet mounting brackets and p

Pagina 234

Chapter 3Installing the SystemUnpacking and Inspecting the System87WARNING Do not remove the bolts on the mounting brackets that attach to the pallet.

Pagina 235

Chapter 3Installing the SystemUnpacking and Inspecting the System88Step 5. Carefully roll the cabinet down the ramp (Figure 3-11).Figure 3-11 Rolling

Pagina 236

Chapter 3Installing the SystemUnpacking and Inspecting the System89Returning EquipmentIf the equipment is found to be damaged, use the original packin

Pagina 237

Tables9Table 1-1. HSO LED Status Indicator Meaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Table 1-2. Suppo

Pagina 238

Chapter 3Installing the SystemUnpacking and Inspecting the System90WARNING Do not attempt to push the loaded cabinet up the ramp onto the pallet. Thre

Pagina 239

Chapter 3Installing the SystemSetting Up the System91Setting Up the SystemAfter a site has been prepared, the system has been unpacked, and all compon

Pagina 240

Chapter 3Installing the SystemSetting Up the System92This cardboard protects the housing baffle during shipping. If it is not removed, the fans will n

Pagina 241

Chapter 3Installing the SystemSetting Up the System93Step 4. Using the handles on the housing labeled Blower 0 Blower 1, part number A5201-62030, alig

Pagina 242

Chapter 3Installing the SystemSetting Up the System94Step 7. Tighten the thumbscrews at the front of each blower.Step 8. If required, install housings

Pagina 243

Chapter 3Installing the SystemSetting Up the System95Step 3. Attach the skin without the lap joint (Front) over the top bracket and under the bottom b

Pagina 244

Chapter 3Installing the SystemSetting Up the System96Step 1. Place the side bezel slightly above the blower housing frame.Figure 3-19 Attaching the Si

Pagina 245

Chapter 3Installing the SystemSetting Up the System97Step 6. To secure the side bezels to the side skins, attach the blower bracket locks (HP part num

Pagina 246

Chapter 3Installing the SystemSetting Up the System98NOTE The procedure in this section requires two people and must be performed with the front metal

Pagina 247

Chapter 3Installing the SystemSetting Up the System99Figure 3-22 Installing the Upper Front Door AssemblyStep 6. Feed the grounding strap through the

Comentarios a estos manuales

Sin comentarios