Web interface 24
Intake Temp tab
This screen enables the Admin to change server intake temperature settings for the management module.
To change the server intake temperature settings:
1. Enter a server intake temperature set point in the Server Intake Temperature Set Point field.
2. Enter a temperature range in which the server intake temperature can vary in the Hysteresis Value
field.
3. Enter a maximum air temperature at which a critical alarm is issued and a trap is sent if the server
intake temperature is exceeded for the High Temperature Threshold field.
4. Enter an air temperature at which a warning is issued and a trap is sent if the server intake
temperature is exceeded for the Warning Temperature Threshold field.
5. Enter an air temperature at which an alarm is issued and a trap is sent if the server intake
temperature drops below for the Low Temperature Threshold field.
6. Enter an air temperature at which an alarm is issued and a trap is sent if the server intake
temperature is exceeded for the Water Flow Loss Emergency Door Opening Temperature Threshold
field.
7. Enter an air temperature at which an alarm is issued and a trap is sent if the server intake
temperature is exceeded for the High Temperature Emergency Door Opening Threshold field.
8. Enter an air temperature at which an alarm is issued and a trap is sent if the condensation pump
cycles are exceeded for the Excessive Moisture: Condensation Pump Cycles Warning Threshold.
9. Enter an air temperature at which an alarm is issued and a trap is sent if the condensation pump
running time is exceeded for the Excessive Moisture: Condensation Pump Running Time Warning
Threshold.