Web interface 9
• Identification menu
Overview menu
Click Overview in the left navigation frame to display the Overview screen. This screen displays graphic
meters for temperature and cooling system parameters.
Parameter Function
Server Intake Temperature
(Average)
Displays the average server intake temperature
Server Exhaust Temperature
(Average)
Displays the average server exhaust temperature
Cooling Displays the total heat removed by the water
Water Inlet Temperature Displays the temperature of the water coming into the
MCS unit to be used to cool the servers
Water Outlet Temperature Displays the temperature of the water after removing
the server heat
Water Flow Displays the water flow rate in liters or gallons per
minute
Water Valve Displays the water valve state
Water System Integrity Displays the Leak Detected Alarm, the Condensation
Pump Warning, and condensation pump activity
• Cycles displays the number of times the pump
runs.
• Duration displays the total amount of time the
pump has run since it was last activated.
Fan Speed Target Displays the percentage of the maximum fan speed