8
RJ45 crimping
pliers
Multimeter
Network cable
tester
Mark pen
ESD-preventive
wrist strap
NOTE:
No installation tool or ESD-preventive wrist strap is provided with the firewall. Prepare them yourself.
Accessories supplied by the firewall
Console cable Grounding cable Feet Mounting bracket
Checklist before installation
Table 7 Checklist before installation
Item Requirements Result
Ventilation
There is a minimum clearance of 10 cm (3.9 in) around
the inlet and exhaust vents for heat dissipation of the
firewall chassis.
A ventilation system is available at the installation site.
Operating
temperature
0°C to 45°C (32°F to 113°F)
Operating
humidity
5% to 95%
Cleanness Dust concentration 3 × 10
4
particles/m
3
Installation site
ESD prevention
The equipment and floor are well grounded.
The equipment room is dust-proof.
The humidity and temperature are at a proper level,
respectively.
Wear an ESD-preventive wrist strap and uniform when
touching a circuit board.
Place the removed interface module on an antistatic
workbench, with the face upward, or put it into an
antistatic bag.
Touch only the edges, instead of electronic components
when observing or moving a removed interface module.