Storage Devices
7–10 UltraSCSI RAID Enclosure
Procedures for Replacing a Disk Drive SBB
Complete the procedure in Table 7–3 to remove a disk drive SBB.
When initially installing disk drive SBBs in an enclosure or installing
a single disk drive SBB, complete the procedure in Table 7–4.
Table 7–3 Removing a Disk Drive SBB
1. To perform a hot swap, go to step 8.
2. To perform a warm swap, quiesce the SCSI bus using array controller
documentation, then go to step 8.
3. To perform a cold swap, shut down the subsystem using array
controller documentation.
4. If there are no expansion enclosures, go to step 5.
If there are expansion enclosures, press and hold the PVA standby
power switch (C
ALLOUT
1) on an expansion enclosure until the
master EMU initiates a power shut down on all enclosures.
5. Press and hold the PVA standby power switch (C
ALLOUT
1) on the
master enclosure until the master EMU initiates a power shut down
on the master enclosure.
CXO6303A