Figure 4 shows the maneuvering space required when unloading the MCS 5042 from a pallet. When
planning for moving the rack, use the delivery forms provided in Appendix A
.
Figure 4: MCS 5042 shipping package delivery and maneuvering space requirements for a single IT rack configuration
Item
Reference
1
MCS 5042 shock-pallet
2
3 piece ramp
3
HP mc-Series 5042 Rack
Caution:
HP recommends that a ramp angle of no
greater than 5° be used to move the MCS
5042 up or down elevations. Typical data
center ramps have a 5º angle (1 to 12
pitches).