9
MCS 5042 specifications
Physical specifications
Table 1: MCS 5042 physical specifications of a standard single rack and server cabinet configuration
Parameter
Packaged system
(as shipped on pallet)
Unpackaged system
(off pallet, unwrapped)
Unpackaged
CTO system
Height 2285 mm (90 in) 2007 mm (79 in) 2007 mm (79 in)
Width 1219 mm (48 in) 904 mm (35.6 in) 904 mm (35.6 in)
Depth 1829 mm (72 in) 1510 mm (59.5 in) 1510 mm (59.5 in)
Weight 732 kg (1614 lb)
1
478 kg (1054 lb)
2
1521 kg (3353 lb)
3
1
Weight for a completely packaged system with unpopulated server rack
2
Weight for an unpackaged system with unpopulated server rack
3
Approximate weight for an unpackaged CTO system (Actual weight varies, according to configuration.)
Note:
If the top shipping bracket interferes with deploying the MCS 5042, you
can remove it. With the top shipping bracket, the total height of the
unpackaged system is 2069 mm (81.5 inches).
Electrical specifications
Table 2: MCS 5042 electrical specifications
Parameter Value Comments
Operating voltage 208/230 VAC +/- 10%, 50/60 Hz
AC line phase Single
Maximum input current 18 A Per line cord
Maximum inrush current 200 A Per line cord
Dropout/hold-up time at minimum line voltage 20 ms
Transfer time of AC transfer switch 2 s
Circuit breaker rating LAHJ Per cord
Power factor > 0.95 At all loads
Ground leakage current < 19.4 mA Per line cord
Rated power consumption 2800W Steady state
Power cords
(included with the MCS 5042)
208 V, 20 A NEMA L6-20-to-Procon
700105 (Qty 2)
250 V, 16 A IEC 309-to-Procon 700105
(Qty 2)