HP Modular Cooling System Manual de instalación Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
34
Note:
Installation service for this MCS 5042 is order number UE005E.
Piping approaches
HP recommends the following methods for facility plumbing orientation with the MCS 5042:
Direct rear approach
Left rear approach
Right rear approach
Note:
You can approach the MCS 5042 from the front with piping for the top
and bottom connection. However, this approach requires careful planning
for accessible component locations and hose attachments.
Figure 24 shows the recommended facility piping approaches to the MCS 5042.
Figure 24: Piping locations for the MCS 5042
Alternate piping location
Locating chilled water piping taps in front of the
MCS 5042 (under the floor) is possible. This option
requires careful planning due to the chilled water
hose length limitation.
Preferred piping location
Locate chilled water piping taps behind the MCS
5042 either under the floor or above the floor. The
chilled water taps must approach laterally.
Do not locate piping connections or components
under the MCS 5042
Vista de pagina 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 59 60

Comentarios a estos manuales

Sin comentarios