Hardware options installation 47
SFF drive
8. Connect the rest of the drive cables required in this drive configuration. For more information, see
"Storage cabling (on page 83)."
9. Install the PCI riser cages. ("Install the PCI riser cages" on page 26)
10. Install the air baffle (on page 24).
11. Install the access panel (on page 24).
12. Install the server into the rack ("Installing the server into the rack" on page 33).
13. Power up the server (on page 20).
CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless
all bays are populated with either a component or a blank.
14. Install the drives ("Installing a hot-plug drive" on page 37).
Mini-SAS cable option
To connect the cable option:
1. Power down the server (on page 20).
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Do one of the following:
o Extend the server from the rack (on page 20).
o Remove the server from the rack (on page 22).
4. Remove the access panel (on page 23).
5. Remove the air baffle (on page 24).
6. Remove the PCI riser cage ("Remove the PCI riser cages" on page 25).
7. Install the storage controller ("Installing a storage controller" on page 50).