Facility planning for implementation 73
Number of fans
HP Modular
Cooling System
200/100
HP Modular
Cooling System
200/100 with
Expansion Rack
MCS-200/100
MCS-200/100 with
Expansion Rack
4 fans
30kW, 2,800 CFM
N+1 Redundancy
15kW, 1,400 CFM
N+1 Redundancy
30kW, 3,000 CFM
15kW, 1,600 CFM
5 fans
N/A N/A 40kW, 3, 750 CFM
or 30kW N+1
20kW, 2,000 CFM
or 15kW N+1
6 fans
N/A N/A 50kW, 4,500 CFM
or 40kW N+1,
30kW N+2
30kW, 2,400 CFM
or 20kW N+1, or
15kW N+2
Cooling performance is rated at 43 ˚F EWT. MCS with Expansion Rack capacity/airflow is pooled and does
not have to be evenly split between racks. For example, the HP Modular Cooling System 200/100 with 3
fans, provides at total of 2,800 CFM. One rack can use 2,000 CFM and the other can use 800 CFM.
A minimum heat load is necessary for operating the MCS-200/100 properly. This minimum depends on the
water supply temperature as shown in the following table.
MCS-200 minimum heat loads
Server air intake
temperature
Water supply
temperature
Minimum heat load
20°C (68ºF)
7ºC (45°F) 9 kW
10ºC (50°F) 7 kW
13ºC (55°F) 6 kW
16ºC (61°F) 6 kW
25°C (77ºF)
7–13°C (4555°F) 16 kW
16ºC (61°F) 14 kW
18ºC (64°F) 10 kW
MCS-100 minimum heat loads
Server air intake
temperature
Water supply
temperature
Minimum heat load
20 C (68 F)
7ºC (45°F) 13 kW
11ºC (52°F) 7.5 kW
15ºC (59°F) 5 kW
19ºC (66°F) 3 kW
25 C (77 F)
11ºC (52°F) 13 kW
15ºC (59°F) 12 kW
11ºC (66°F) 6 kW
23ºC (73°F) 3 kW
30 C (86 F)
17ºC (63°F) 15 kW
21ºC (70°F) 13 kW
25ºC (77°F) 6 kW
29ºC (84°F) 3 kW