Redundant hot-plug fans option
The server supports redundant hot-plug fans to provide proper airflow to the system if a primary fan fails.
In the standard, non-redundant, configuration, fans 1, 2, and 3 cool the server.
For the redundant configuration, fans 4, 5, and 6 are added to back up the primary fans. This
configuration enables the server to continue operation in non-redundant mode, if a fan failure occurs. The
following rules apply:
• If one fan fails in non-redundant mode, the server shuts down.
• If one fan fails in redundant mode, the server converts to non-redundant mode.
• If two fans fail in redundant mode, the server shuts down.
WARNING: To prevent personal injury from hazardous energy:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Do not place tools or metal parts on top of batteries.
To install the fans:
1. Do one of the following:
o Open or remove the tower bezel, as needed ("Open or remove the tower bezel" on page 21).
o Extend the server from the rack (on page 22).
2. Remove the access panel. ("Remove the access panel" on page 25)
3. Install three hot-plug fans into the center wall.