Hp ProLiant ML370 G5 Server Manual de usuario Pagina 59

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 135
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 58
Hardware options installation 59
14.
Install the access panel (on page 26).
15. Do one of the following:
o Close or install the tower bezel, as needed.
o Slide the server back into the rack.
16. Power up the server (on page 20).
Redundant hot-plug fans option
The server supports redundant hot-plug fans to provide proper airflow to the system if a primary fan fails.
In the standard, non-redundant, configuration, fans 1, 2, and 3 cool the server.
For the redundant configuration, fans 4, 5, and 6 are added to back up the primary fans. This
configuration enables the server to continue operation in non-redundant mode, if a fan failure occurs. The
following rules apply:
If one fan fails in non-redundant mode, the server shuts down.
If one fan fails in redundant mode, the server converts to non-redundant mode.
If two fans fail in redundant mode, the server shuts down.
WARNING: To prevent personal injury from hazardous energy:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Do not place tools or metal parts on top of batteries.
To install the fans:
1. Do one of the following:
o Open or remove the tower bezel, as needed ("Open or remove the tower bezel" on page 21).
o Extend the server from the rack (on page 22).
2. Remove the access panel. ("Remove the access panel" on page 25)
3. Install three hot-plug fans into the center wall.
Vista de pagina 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 134 135

Comentarios a estos manuales

Sin comentarios