HP Environmental Base Station installed on a rack 21
o
The HP Rack Sensor Array has the Front (Cold) Side label and the Rear (Hot) Side label, indicating
where the sensor string is installed.
o The HP Three Point Sensor Array does not have a label and can be installed anywhere on the rack
or in the data center.
NOTE:
The preconfigured lengths between the sensor pods are designed to fit a standard 42U
rack and should be evenly spaced: one at the top of the rack door, one in the middle of the rack
door, and one at the bottom of the rack door. If you are installing the sensor pods on a rack of a
different size and require an extension, consult your data center administrator.
3. Remove the mounting tape liner and attach the top pod bracket to the designated location. Repeat this
step for the remaining two pod brackets.
4. If the sensor pod is not connected to the pod bracket, slide the top sensor pod into the pod bracket
installed at the top of the rack door (3). Repeat this step for the remaining two pods.