Troubleshooting 74
Network card on the Edge server
Network switch between the Edge server and the gateway
Verifying HP Water Leak Detection Base Station functionality
When verifying the functionality of the water leak detector base station, the LED status must match the status
reported in the Observer software.
LED status Observer status Meaning
Solid light
Status icon is green
(normal status)
No alarms present
Flashing
(on 1/2 second, off 1/2 second)
Status icon is ____
(water leak condition is active)
Leak alarm
Flashing
(on 1/2 second, off 2 and 1/2
seconds)
Status icon is red
(alarm status)
Cable break alarm
Verifying ION power meter communication
Communication from the ION power meter to the Observer software includes:
Serial Modbus communication from the power meter to the Modbus base station device
Ethernet Modbus/TCP communication from the Modbus base station device to the Observer software
To make sure that the ION power meters communicate correctly with the server and Observer software, verify
the following connections.
Verify the ION power meters (in a daisy chain configuration) are connected to the Modbus base station
via an RS-485 serial connection.
o If multiple ION power meters are connected to the Modbus base station (in a daisy chain), verify
that each power meter has a unique device ID ("Programming the Modbus ID" on page 59) and that
the last meter in the configuration has the terminating resistor connected ("Programming Modbus
communication" on page 59).
o If multiple ION power meters are connected to the Modbus base station (in a daisy chain) and some
of the power meters are not communicating, verify that the RS-485 connections down the daisy
chain are securely connected.
o Verify that all cable connection points are installed and securely fastened to the terminal block.
Verify the Modbus base station is connected to the server network connection via Ethernet cable.
o Verify the Modbus base station is powered on.
o From the server, ping the Modbus base station to verify it is connected to the network.
o Verify the Modbus base station has the duplex setting set to Auto Duplex ("Verifying network
settings" on page 73).
Verify that the Modbus plug in component was installed during the Device Manager installation. If the
Modbus plug in component was not installed, the Observer software cannot communicate to the ION
power meters, and no Modbus communication occurs to the Edge server.