(Optional) Sensor Base Stations 48
k.
Replace the Water Leak Detector lid, and use the supplied Allen wrench to tighten the two screws to
secure the lid.
Callout Component Description
1
5VDC IN Insert the white wire into the + (positive) terminal.
Insert the black wire into the - (negative) terminal.
2
Fault and Leak
3
W terminal Insert the white wire from the wire harness.
4
B terminal Insert the black wire from the wire harness.
5
G terminal Insert the green wire from the wire harness.
6
R terminal Insert the red wire from the wire harness.
7
NC jumper wire Connect the Fault and Leak terminals.
4. Insert the leak detection cable in to the water leak detector sensor and tighten the connector.
5. Route the sensing cable along the sub-floor, in strategic locations, to detect the presence of fluid.
6. Connect the Water Leak Detector to the base station.
7. Connect one end of the AC adapter to the power input connector on the Water Leak Detector wire
harness, and then plug the other end of the AC adapter into a power source. The base station
automatically powers up and follows the Base Station LED sequence.
Installation is complete.