(Optional) Sensor Base Stations 53
c.
Using a flathead screwdriver, secure the black wire to the negative terminal block on the current
sensor transducer.
Repeat for the other two current transducers (CH 4 and CH 5/Current B and Current C).
d. Insert the connector from the wire harness into the 200A Current Base Station.
3. Connect one end of the 24V AC adapter to the power input connector on the 200A Current Base
Station, and then plug the other end of the AC adapter into a power source. The base station
automatically powers up and follows the Base Station LED sequence.
IMPORTANT: Verify that the jumper setting of the CT matches the amperage of the electrical
equipment you connect it to.
4. Adjust the jumper setting of each CT to match the amperage of the electrical device it is connected to.
o Low—O-100 amps
o Medium—0-150 amps
o High—0-200 amps
Comentarios a estos manuales