8ARated current
VA max 1600WPower consumption
IEC 320 C19 male connector inside back
door
Electrical connection to power
Climatic environment
15
o
C to 32
o
C (59
o
F to 90
o
F)
Dry bulbTemperature (operat-
ing)
25
o
C (77
o
F) maximum
Wet bulb
11
o
C per hour
Thermal transition
–40
o
C to 66
o
C (-40
o
F to 151
o
F)
Dry BulbTemperature (ship-
ping and storage)
46
o
F (115
o
F) maximum
Wet bulb
30
o
C (54
o
F) per hour
Thermal transition
20% to 80%, non-condensingOperatingRelative humidity
5% to 95%, non-condensingShipping and storage
Sea level to 10,000 ft. (3,048 m)OperatingAltitude
Sea level to 12,000 ft. (3657 m)Shipping and storage
5500 BTU/hr (1400 KCal/hr or 1600 watts)OperatingHeat dissipation, dir-
ect ESD
up to 4.0 kV to all external metal panels and
doors
Contact discharge
up to 8.0 kV to the front graphical user inter-
face display
Air discharge
7.6 BelOperatingSound power level
7.8 BelIdle
5.5dbOperatingSound pressure at
operator
HP StorageWorks ESL E-Series Tape Library 95