Installation site requirements
The following tables provide information about temperature and humidity, cleanness, and air quality
requirements.
CAUTION:
If condensation appears on the router when you move it to a high-temperature environment, dry the
router before powering it on to avoid short circuits.
To ensure normal operation of the router, make sure the room temperature meets the requirements
described in Table 2.
Table 2 Temperature requirements
Tem
p
erature Ran
g
e
Operating temperature
Long term: 0°C to 45°C (32°F to 113°F)
Short term: –10°C to +55°C (14°F to 131°F) (no more than 96 hours of
continuous operation in less than 15 days in one year)
Storage temperature –40°C to +70°C (–40°F to +158°F)
Maintain appropriate humidity in your equipment room, as described in Table 3.
Table 3 Humidity requirements
Humidit
y
Ran
g
e
Operating humidity (noncondensing) 5% to 95%
Storage humidity (noncondensing) 5% to 95%
Lasting high relative humidity tends to cause poor insulation, increased electricity consumption,
mechanical property change of materials, and corrosion of metal parts. Lasting low relative humidity
is likely to result in loose screws due to washer contraction, and even ESD, which causes the circuits to
fail.
Table 4 Dust concentration limit in the equipment room
Ph
y
sical active substance Concentration limit (
articles/m
3
)
Dust particle 3 x 10
4
(No visible dust on desk over three days)
Note: Dust particle diameter 5μm
Table 5 Limits on harmful gases in the equipment room
Gas Ma
x
concentration (m
g
/m
3
)
SO
2
0.2
H
2
S 0.06
NH
3
0.05
Cl
2
0.01
2