148 Site Requirements
* In-rush current occurs for 10 to 12 milliseconds
Table 14
Total Operating and In-Rush Currents
Operating
Current
@ 110v
Operating
Current
@ 220v
In-Rush
*
Current
Power
Cords
Controller w/ 6 Disk Enclosures
41.3A 20.4A 124A 14
Controller w/ 5 Disk Enclosures
34.8A 17.2A 104A 12
Controller w/ 4 Disk Enclosures
28.3A 14.0A 84A 10
Controller w/ 3 Disk Enclosures
21.8A 10.8A 64A 8
Controller w/ 2 Disk Enclosures
15.3A 7.6 44A 6
Controller w/ 1 Disk Enclosure
8.8 4.4A 24A 4
Table 15
Controller Enclosure Electrical Requirements
Measurement Value @ 110v Value @ 220v
Voltage
– Range
– Frequency
100-127V
50 - 60 Hz
220-240V
50 - 60 Hz
Current
–Typical
– Maximum Operating
–Inrush
1.5A
2.3A
21.4A
0.8A
1.2A
42.9A
Comentarios a estos manuales